|
Potential-pH Diagrams
|

|
|
|
Intelligent Tools
|
|

|
|
|
|

|
|
|

|
|
|
Corrosion Calculator
|
|

|
|
|
Corrosion Economics Estimator
|
|

|
|
|
|
|
|
TUTORIAL ON HEAT TRANSFER and CORROSION TESTING UNDER ITS INFLUENCE
David C. Silverman
|
|
Table of Contents
Heat Exchangers- Effect of Fouling on Heat Transfer Rates
After some operational period, surfaces of heat exchangers are no longer in the
pristine condition found upon installation. The surfaces can become coated with
deposits from the process or cooling streams (e.g. particulates) or become coated
with corrosion products or microbiological films. No matter the cause, this
additional structure on the surface creates an additional resistance to heat
transfer and a decrease in performance. This resistance is represented by the
term "fouling factor" or "fouling resistance" (Rf) which must be
considered when designing or otherwise analyzing performance of a heat exchanger.
The important point is that this fouling tends to increase the temperature at the
wall. Such an increase in temperature can increase the fouling or corrosion rate
in addition to decreasing operational effectiveness of the exchanger.
As discussed in the section
Heat Exchangers-Analysis in the Absence of Fouling
the overall heat transfer rate coefficient is related to the heat transfer
rate and temperature difference by
or
(20)
where U is the overall heat transfer coefficient, QTotal is the heat
transfer rate, A is the area, and ΔT is the temperature difference. "Mean" is
the mean temperature difference across the tube and "LMTD" is the log mean temperature
difference using only the temperatures at the hot and cold ends. Both subscripts
are defined in
Heat Exchangers-Analysis in the Absence of Fouling . The
fouling factor is defined as
(21)
Note that the heat transfer coefficient of the fouled exchanger is smaller than
that of the clean exchanger making Rf positive. The value of
1/Rf is subtracted from Uclean to obtain Ufouled.
Fouling factors are obtained experimentally by determining the value of the heat
transfer coefficient for both the clean and fouled exchanger. Some reported
values are in the table below. They are provided as examples of order of magnitude
only and should not be used for any design calculations. Also note that fouling
factors vary with the inverse of the fluid velocity raised to a power "n", where
"n" lies in the range of about 1 to 2 (1/(velocity)n).
| Fluid Type |
Fouling Factor hr-ft2-oF/BTU |
Fouling Factor s-cm2-oC/cal |
Sea Water – Value somewhat temperature dependent |
<0.0005 to >0.001 |
3 to 8 |
| Treated Boiler Feed Water |
~0.001 |
~7 to 8 |
| Some types of oils |
0.004 to 0.005 |
30 to 40 |
Steam (oil-free) |
~0.0005 |
3 to 4 |
Industrial Air Depends on cleanliness |
0.002 |
~15 |
As shown in equations (20), the overall heat transfer coefficient is proportional
to the overall heat transfer rate and inversely proportional to the temperature
difference between the streams and the required area. The example from
Heat Exchangers-Analysis
in the Absence of Fouling can be used to provide an idea of
the effect of fouling on heat transfer and wall temperature. Water at the
rate rate of 1.5 kg/min is heated from 25C to 50C by an oil. The fluids are
in a counter-current flow arrangement and the oil enters at 150C and leaves at 100C.
The overall heat transfer coefficient as calculated from equation (19)
is 2.065 cal/hr-m2-C. The calculated area is
14.8m2. Now suppose that the cooling water is seawater with
a fouling factor of 0.001 hr-ft2-oF/BTU or 7.4
s-cm2-oC/cal . This fouling factor is Rf
in equation (21). Equation (21) is used to estimate the fouled overall heat
transfer coefficient. Converting the fouling factor to square meters and
hours and inverting the equation results in
Solving for Ufouled results in a value of 1.98x105
cal/hr-m2-C, about a 5% decrease in the heat transfer coefficient.
If the surface area remains at about 14.8 m2, the log mean temperature
difference becomes 85.3C. Assuming that the oil still must be heated between 100C
and 150C and the inlet water temperature is 25C, the outlet water temperature would
increase by several degrees.
While this increase in temperature seems small, it can have a significant
impact on the fouling rate. The reason is that fouling is an activated
process. It can be assumed to be proportional to exp(-Eactiviation/T).
If one assumes
an activation energy of about 10000 cal/mol, a
5C change in surface temperature results in about a 20% increase in fouling
rate (deposition and crystal growth) at 85C. The result is more rapid build-up
resulting in higher temperatures and an accelerating fouling process. A
corrosion process could increase in a similar fashion because it, too, is an
activated process. Minimizing fouling is important in heat exchangers.
Detailed information on materials of construction of water cooled heat exchangers,
water chemistry, and chemical water treatments can be found in "Guidelines
for Troubleshooting Water Cooled Heat Exchangers", A. J. Freedman, A. S. Krisher,
and D. Steinmeyer, Materials Technology Institute, 2004. Fouling can also
occur in air cooled exchangers depending on cleanliness of the air and moisture
content especially if condensation is possible.
In addition, fouling can roughen the surface. The effect on heat transfer
is complex. On the one hand, surface roughening in and of itself can increase the
heat transfer coefficient in the fluid. But, since the roughening is usually
accompanied by an increase in thickness of the wall, the resistance to heat
transfer through the wall can be increased, sometimes significantly. In addition, the structure
of the fouling can be strongly influenced by the local velocity field. Laboratory
simulation as outlined in
Laboratory Corrosion Testing Under Heat Transfer Conditions - a Critique can be
difficult for fouled heat exchangers. Resorting to a test heat exchanger has sometimes been the only way
to simulate some of these complex situations.
Previous Page: Heat Exchangers-Analysis in the Absence of Fouling
Next Page: Natural Convection
Return to Table of Contents
|
David C. Silverman, Ph.D. - Primary Consultant
E-Mail: dcsilverman@argentumsolutions.com
Phone: 314-576-3586
Fax: 314-754-9825
Address: The Argentum House
14314 Strawbridge Ct.
Chesterfield, MO 63017
|
|